FN7-24 INDOOR HV LOAD BREAK SWITCH
Outline
FN7-24(DR) indoor HV load break switch applies to electric system with 24kV rated voltage and three-phase AC 50/60Hz, for connecting and breaking load current and short circuit current.
Use Conditions
NO. |
Items |
Unit |
Value |
1 |
rated voltage |
kV |
24 |
2 |
rated frequency |
Hz |
50 |
3 |
rated current |
A |
400, 630, 1250 |
4 |
rated active load breaking current |
A |
400, 630, 1250 |
5 |
Rated closed loop breaking current |
A |
400, 630, 1250 |
6 |
5% rated active load breaking current |
A |
20, 31.5, 62.5 |
7 |
rated cable charging breaking current |
A |
10 |
8 |
1min power frequency withstand voltage: phase-to-phase, phase to earth/ fracture |
kV |
50/60 |
9 |
lightning impulse withstand voltage: phase-to-phase, phase to earth/ disconnecting fracture |
kV |
125/145 |
10 |
rated short time withstand current (thermal stability) |
kA |
16, 20, 25 |
11 |
rated short circuit duration |
s |
1 |
12 |
rated peak withstand current |
kA |
40, 50, 63 |
13 |
rated short circuit making current |
kA |
40, 50, 63 |
14 |
mechanical life |
times |
2000 |
Overall Drawing
FN7-24D

FN7-24R