FN12-12 Series Indoor High Voltage Air Load Break Switch

Short Description:

FN12-12 indoor HV air load break switch is a 3-phase AC 50Hz 12kV indoor switch equipment.
♦ Installation way: front-mounted, side mounted, flip mounted;
♦ Operating mechanism: spring operating mechanism, manual type and electrical type available;
♦ Operation type: right operation and left operation;
♦ Application: indoor 12kv switchgear.


Product Detail

Product Tags

Outline

FN12-12 indoor HV air load break switch is a 3-phase AC 50Hz 12kV indoor switch equipment.
♦ Installation way: front-mounted, side mounted, flip mounted;
♦ Operating mechanism: spring operating mechanism, manual type and electrical type available;
♦ Operation type: right operation and left operation;
♦ Application: indoor 12kv switchgear.

Environmental Conditions

♦ Ambient temperature: -25°C 〜+40°C;
♦ Altitude: <1000m (above sea level);
♦ Relative humidity: daily average <95%, monthly average <90%;
♦ Earthquake intensity: <8 level;
♦ Pollution grade: II;
♦ Places without fire, explosion, chemical corrosion and serious vibration.

Main Technical Parameters

NO

Item

Unit

FN12-12D/6

30-20

FN12-12RD/1

25-31.5

1

Rated voltage

kV

12

12

2

Rated frequency

Hz

50

50

3

Rated current

A

630

125

4

1min power frequency withstand voltage (Phase to earth, between poles, open contacts)

Phase-to-earth, phase-to-phase

kV

42

42

Isolating fracture

48

48

5

Rated lightning impulse withstand voltage (Phase to earth, between poles, open contacts)

Phase-to-earth, phase-to-phase

kV

75

75

Isolating fracture

85

85

6

Rated short time withstand current (thermal stability current)

Load break switch

kA

20

 

Earth switch

20

 

7

Rated short circuit duration ( thermal stability time)

Load break switch

s

4

 

Earth switch

2

 

8

Rated short circuit making current (peak)

kA

50

 

9

Rated breaking current

Active load breaking current

A

630

 

Loop breaking current

630

 

5% active load breaking current

31.5

 

Cable charging current

 

10

 

No-load transformer capacity

kVA

1250

 

10

Rated short circuit breaking current (limit current fuse)

kA

 

31.5

11

Rated transfer current

A

 

1200

12

Mechanical life

times

2000

2000

13

Striker output energy

J

 

1±0.5

General Structure Drawing and Installation Size (unit: mm)

♦ FN12-12D (side-mounted left operation)

图片41

♦ FN12-12D (flip-mounted left operation)

图片42

♦ FN12-12RD (front side-mounted left operation)

图片43

♦ FN12-12RD (front flip-mounted left operation)

图片44