Products
3kv-36kv Zinc Oxide Lightning Arrester

3kv-36kv Zinc Oxide Lightning Arrester

3kv-36kv Zinc Oxide Lightning Arrester is a device to protect electrical equipment from overvoltage transients caused by external (lightning) or internal (switching) events. Also called a surge protection device (SPD) or transient voltage surge suppressor (TVSS), this class of device is used to protect equipment in power transmission and distribution systems. (For consumer equipment protection, different products called surge protectors are used.) The energy criterion for various insulation material can be compared by impulse ratio, the surge arrester should have a low impulse ratio, so that a surge incident on the surge arrester may be bypassed, to the ground instead of passing through the apparatus.


Usage& Feature

The 3kv-36kv zinc oxide lightning arrester protects the electrical equipments in AC power systems against being damaged by atmospheric overvoltage and operational overvoltage.


Metal-oxide Lightning Arrester without Gaps (nominal discharge current 5kA) (export type)

Type

Rated voltage kV(ms)

Maximum

continuous operation voltage kV(ms)

1/4 steep current impulse kV(crest)

8/20μs lighting current impulse kV(ms)

30/60μs switching current impulse kV(ms)

2ms square wave current impulse withstand A(crest)

4/10μs high current impulse kA(crest)

YH5W-3

3

2.55

11.3

9

8.9

150

65

YH5W-6

6

5.1

22.6

18

16.8

150

65

YH5W-9

9

7.65

33.7

27

23.8

150

65

YH5W-10

10

8.4

36

30

23

150

65

YH5W-11

11

9.4

40

33

30

150

65

YH5W-12

12

10.2

42.2

36

27

150

65

YH5W-15

15

12.7

51

45

38.5

150

65

YH5W-18

18

15.3

61.5

54

46.2

150

65

YH5W-21

21

17.0

71.8

63

54.2

150

65

YH5W-24

24

19.5

82

72

62

150

65

YH5W-27

27

22

92

81

69.8

150

65

YH5W-30

30

24.4

102

90

79

150

65

YH5W-33

33

27.5

112

99

86.7

150

65

YH5W-36

36

29.0

123

108

92.4

150

65


Metal-oxide Lightning Arrester without Gaps (nominal discharge current 10kA) (export type)

Type

Rated voltage kV(ms)

Maximum

continuous operation voltage kV(ms)

1/4 steep current impulse kV(crest)

8/20μs lighting current impulse kV(ms)

30/60μs switching current impulse kV(ms)

2ms square wave current impulse withstand A(crest)

4/10μs high current impulse kA(crest)

YH10W-3

3

2.55

11.3

9

8.9

250

100

YH10W-6

6

5.1

22.3

18

16.8

250

100

YH10W-9

9

7.65

33.7

27

23.8

250

100

YH10W-10

10

8.4

36

30

23

250

100

YH10W-11

11

9.4

40

33

30

250

100

YH10W-12

12

10.2

42.2

36

27

250

100

YH10W-15

15

12.7

51

45

38.5

250

100

YH10W-18

18

15.3

61.5

54

46.2

250

100

YH10W-21

21

17

71.8

63

54.2

250

100

YH10W-24

24

19.5

82

72

62

250

100

YH10W-27

27

22

92

81

69.8

250

100

YH10W-30

30

24.4

102

90

79

250

100

YH10W-33

33

27.5

112

99

86.7

250

100

YH10W-36

36

29

123

108

92.4

250

100





Hot Tags: 3kv-36kv Zinc Oxide Lightning Arrester, China, Manufacturer, Supplier, Factory
Send Inquiry
Contact Info
We strive to provide customers with quality products. Request Information, Sample & Quote, Contact us!
X
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept