C65-63 Circuit Breaker (6KA MCBs)
Scope of Application
C65-63 6KA Circuit Breaker (also called 6KA Household MCB, similar to CHINT NB1-63) is used for the circuit of AC 50Hz, rated voltage of 110V/230/400V, rated current of 1A, 2A, 3A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 60A, 63A to protect overload and short-circuit, as well as use for normal circumstances of the infrequent circuit conversion, also be used as the isolating switch for cut-off circuit to protect circuit and equipment.
6KA Circuit Breaker (6KA Household MCB) are used for industrial, commercial, high-rise and civilian residential and other places.
Meet the standards: GB10963.1, IEC60898-1.
Main Technical Parameters
Rated Current |
6A,10A,16A,25A,40A,50A,63A |
Poles |
1P.2P.3P,4P,1P+N,3P+N |
Rated Voltage Ue |
230V/400V |
Rated Impulse Withstand Voltage(1.2/50)Uimp |
6kV |
Dielectric Test Voltage At And Ind . Freq . For 1min |
6kV |
Breaking Indication |
Green Window(Disconnected),Red Window(Closed) |
Protection Class |
IP20 |
Thermo - Magnetic Release Characteristic |
B-Curve (3-5In),C-Curve (5-10In),D-Curve (10-14In) |
Electrical Life |
2000 |
Mechanical Life |
10000 |
Reference Temperature For Setting Of Thermal Element |
30℃ |
Ambient Temperature |
-5~+40℃ |
Terminal Connection Type |
Phillips Screws |
Adapter Cable |
6-63A 1-25mm² 16-3AWG | 80-125A 8-35mm² 16-2AWG |
Tightening Torque |
3.0N.M |
Combination With Accessories Auxillary Contact |
|
Auxillary Contact |
Yes |
Alarm Contact |
Yes |
Shunt Release |
Yes |
Under Voltage Release |
Yes |
Tripping Characteristic Curve -- B C D Type



Temperature compensation
When the ambient temperature is not a benchmark of 30 degrees , the reference correction factor is as folows .
Ambient Temperature |
-20℃ |
-10℃ |
0℃ |
10℃ |
20℃ |
30℃ |
40℃ |
50℃ |
60℃ |
Current Correction Coefficient |
1.25 |
1.2 |
1.15 |
1.10 |
1.05 |
1.00 |
0.95 |
0.90 |
0.85 |
Connection
Rated Current |
Minimum Adapter Copper Wire |
6A |
1 MM² / 17AWG |
10A |
1.5 MM² / 16AWG |
16A |
1.5 MM² / 16AWG |
25A |
2.5 MM² / 13AWG |
32A |
4 MM² / 11AWG |
40A |
6 MM² / 10AWG |
50A |
10 MM² / 7AWG |
63A |
10 MM² / 7AWG |
Mounting Method
Th35-7.5 type steel mounting rail is used for installation.