XUW2-1600 Air circuit breaker
10,000+ Satisfied Clients | Trusted by a Global Network
XUW2-1600
TheXUW2-1 600 Series intelligent air circuit breaker (hereinafter referred to as circuit breaker) is suitable for distribution networks with frequency of AC 50Hz, rated working voltage up to 690V and rated current ranging from 200A to 1600A.
It's used to distribute electrical energy and protect lines and power equipment from overload, short circuit, undervoltage,single-phase grounding(leakage) and other faults. The circuit breaker has intelligent protection function and precise selective protection, can improve power supply reliability and avoid unnecessary power outages. Meanwhile, it has open type communication
interface, which is convenient for fieldbus connection, and can be used for four remote operations to meet the requirements of the control center and automation system. Equipped with corresponding leakage transformer and intelligent controller,leakage protection can be achieved.
The circuit breaker has isolation function and is represented by symbol"_ /x”
The circuit breaker with rated working current of 630A and below can also be used for overload, short circuit, phase loss, undervoltage and ground protection of motor in AC 50 (60) Hz, 400V distribution network. Under normal condition, the circuit breaker can also serve for infrequent switching of circuit and infrequent starting of motor.
The circuit breaker complies with GB14048.1-2012 Low-voltage switchgear and controlgear-Part 1: General rules; And GB14048.2-2008 Low-voltage switchgear and controlgear-Part 2: Circuit breakers; GB14048.4-2020 Low-voltage switchgear and controlgear-Part4-1:Contactors and motor-starters-Electromechanical contactors and motor-starters( Including motor protector)
Technical data sheet
Model | XUW2-1600 | |||||||
Rated current of shell frame grade Inm (A) | 1600 | |||||||
Rated current ln (A) | 200、400、500、630、800、1000、1250、1600 | |||||||
Rated operating voltage Ue(V) | AC400,AC690 | |||||||
Operating frequency (Hz) | 50Hz/60Hz | |||||||
Rated insulation voltage Ui(V) | 1000 | |||||||
Rated impact tolerance voltage Uimp(kV) | 12 | |||||||
Power frequency tolerance voltage U(V)1min | 3500 | |||||||
The number of | 3、4 | |||||||
N-pole rated current In(A) | 100%cln | |||||||
Use Category | GB14048.2 | B | ||||||
Rated limit short circuit breaking capacityLcu (kA)(effective value) | AC400V | 65 | ||||||
AC690V | 50 | |||||||
AC400V | 55 | |||||||
Rated short circuit breaking capacity | AC690v | 42 | ||||||
LCS (kA)(effective value) | AC400V | 143 | ||||||
AC690V | 105 | |||||||
Rated short circuit connection capability | AC400V | 50 | ||||||
AC690v | 42 | |||||||
Full breaking time (no additional delay)(MS) | 25 | |||||||
Closing time (MS) | Max 70 | |||||||
Electrical life (times) | AC400V | ln=200A~630A | 1500 | |||||
In=800A~1250A | 1000 | |||||||
In=160OA | 800 | |||||||
AC690v | ln=200A~630A | 100o | ||||||
ln=80OA~1250A | 650 | |||||||
ln=1600A | 500 | |||||||
Mechanical life (times) | Free maintenance | 15000 | ||||||
Have a maintenance | 20000 | |||||||
Dimensions (width X height X depth)mm | Fixed type | 3P | 260×310×240 | Drawer type | 3P | 275×345×330 | ||
4P | 330×310×240 | 4P | 345×345×330 |