DZ49-63 series Miniature Circuit breaker(MCB)

Short Description:

Miniature circuit breaker DA47N-63 are recommended for use in electrical distribution panels of residential and public buildings.


Product Detail

Product Tags

Introduction

DZ49-63  are intended for protecting distribution and group systems having different loads:
- electric appliances, lighting – V characteristic switches;
- drives with moderate starting currents (compressor, fan group) - C characteristic switches;
- drives with high starting currents (hoisting mechanisms, pumps) - D characteristic switches;
Miniature circuit breaker DA47N-63 are recommended for use in electrical distribution panels of residential and public buildings.

Advantages

·  Two types of short circuit protection.
·  Wide range of operating temperatures from –40 to +50° С.
·  Updated wider engagement lever with improved contact area.
·  Notches on terminal clamps provide for lowering thermal losses and boosting the mechanical stability of connection.

MCB DZ49-63  
For protection of general power distribution (IEC/EN 60898-1)          
Poles

1P

2P

3P

4P

 
Electrical performance  
Functions

short circuit protection,overload protection,isolationg,control

 
Rated frequency  f   Hz

50-60Hz

 
Rated working voltage  Ue   V AC

230/400

400

 
Rated current  In A

6,10,16,20,25,32,40,50,63

 
Rated insulated voltage Ui  V

500

 
Impulse withstand voltage Uimp   kV

4

 
Instantaneous tripping type

DA49N-63

B/C/D

 

DA49H-63

B/C/D

 
Rated short circuit Icn(kA)       

DA49N-63

4.5

 

DA49H-63

6

 
Release type

Thermal magnetic type

 
Service life(O~C) Mechanical  Actual value

20000

 Standard value

4000

Electrical  Actual value

8000

 Standard value

4000

Connection and installation  
Protection degree

IP20

 
Wire                                             mm²

1~35

 
Working temperature

-5~+40℃

 
Resistance to humidity and heat

Class 2

 
Altitude above sea

≤2000

 
Relative humidity

+20℃ ,≤90% ;+40℃ ,≤50%

 
Pollution degree

2

 
Installation environment

Avoid obvious shock and vibration

 
Installation class

ClassⅡ , ClassⅢ

 
Mounting

DIN35 rail

 
Combination with accessories  
Auxiliary contact

Yes

 
Alarm contact

Yes

 
Shunt release

Yes

 
Undervoltage release

Yes

 
Auxiliary contact+Alarm contact

Yes

 
Dimensions(mm)                                            (WxHxL)                                                                                 

a

17.5

35

52.5

70

b

80.2

80.2

80.2

80.2

c

76.5

76.5

76.5

76.5