ZW7-40.5 Series Outdoor High Voltage Vacuum Circuit Breaker (Recloser)
Description
ZW7-40.5 outdoor HV vacuum circuit breaker is a 3-phase AC 50Hz 40.5kV outdoor switch equipment.
♦ Installation way: foundation installation;
♦ Operating mechanism: spring operating mechanism and electromagnetic operating mechanism;
♦ Pole material: silicone rubber, ceramic;
♦ Application: outdoor 33kV substation, power plant.
♦ Current transformer: in-buit installation, external installation.


Product Standards
♦ IEC62271-100 High Voltage Switchgear and Controlgear Part 100: AC Circuit-breakers
♦ GB1984 High Voltage AC Circuit-breakers
♦ GB/T11022 Common Specifications for High-voltage Switchgear and Controlgear Standards
♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers
♦ DL/T402 Specification of High-voltage AC Circuit-breakers
Environmental Conditions
♦ Ambient temperature: -40°C~+40°C;
♦ Altitude: <1000m;
♦ Maximum wind speed is 10km/h, minimum wind speed for the rated level (132/230kv) is 3.2km/h;
♦ Earthquake intensity: <8 level;
♦ Minimum nominal creepage distance: 31mm/kV;
♦ Air pollution degree: Class IV.
Main Technical Parameters
No |
Item |
Unit |
Value |
|
1 |
Rated voltage |
kV |
40.5 |
|
e |
Ratedinsulationlevel |
1 min power frequencyDry test (fracture, inter-phase, to earth)Wet test (to earth, external insulation) |
kV |
95 85 |
Lightning impulse withstand voltage(peak) |
185 |
|||
3 |
Rated current |
A |
1250, 1600, 2000, 2500 |
|
4 |
Rated short circuit breaking current |
kA |
20, 25, 31.5 |
No |
Item |
Unit |
Value |
5 |
Rated short circuit making current (peak) |
kA |
50, 63, 80 |
6 |
Rated peak withstand current |
kA |
50, 63, 80 |
7 |
Rated short time withstand current |
kA |
20, 25, 31.5 |
8 |
Rated operating sequence |
|
O-0.3S-CO-180S-CO |
9 |
Rated short circuit breaking current breaking number |
times |
20 |
10 |
Rated short circuit duration |
s |
4 |
11 |
Breaking time |
s |
≤0.09 |
12 |
Mechanical life |
times |
10000 |
13 |
Newly manufactured vacuum interrupter |
Ps |
≤1.33×10-3 |
Vacuum interrupter during 20-year storage time |
<6.6×10-2 |
||
14 |
Circuit breaker net weight |
kg |
800 |
15 |
Clearance between open contacts |
mm |
22±2 |
16 |
Contact travel |
mm |
4±1 |
17 |
Average opening speed |
m/s |
1.4-1.7 |
18 |
Average closing speed |
m/s |
0.4-0.7 |
19 |
Contact closing bounce time |
ms |
≤3 |
20 |
Inter-phase opening and closing synchronism |
ms |
≤2 |
21 |
Closing time |
ms |
50≤t≤200 |
22 |
Opening time |
ms |
30≤t≤60 |
23 |
Each phase main circuit DC resistance (not includeCT internal resistance) |
μΩ |
≤100 |
24 |
Dynamic and fixed contact cumulative thickness allowed to wear |
mm |
3 |
25 |
Rated contact pressure |
N |
2500±200 |
General Structure Drawing and Installation Size (unit: mm)
♦ Side-mechanism type

♦ Mid-mechanism type