ZN85-40.5 Series Indoor High Voltage Vacuum Circuit Breaker
Description
ZN85-40.5 indoor HV vacuum circuit breaker is a 3-phase AC 50Hz 40.5kV indoor switch equipment.
♦ Installation way: withdrawable type;
♦ Operating mechanism: spring operating mechanism;
♦ Pole type: assembled pole, embedded pole;
♦ Application: switchgear KYN61-40.5.
♦ Secondary plug: 58pins, 64pins.
Environmental Conditions
♦ Ambient temperature: -15r~+40r;
♦ Altitude: <1000m;
♦ Relative humidity: daily average <95%, monthly average <90%;
♦ Earthquake intensity: <8 level;
♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.
Main Technical Parameters
No |
Item |
Unit |
Value |
1 |
Rated voltage |
kV |
40.5 |
2 |
Rated current |
A |
1250 1600, 2000, 2500 |
3 |
Rated short circuit breaking current |
kA |
25, 31.5 |
4 |
Dynamic current (peak) |
63, 80 |
|
5 |
4s thermal stability current |
25, 31.5 |
|
6 |
Rated short circuit making current (peak) |
63, 80 |
|
7 |
Rated short circuit current breaking number |
Times |
20 |
8 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
9 |
1 min power frequency withstand voltage |
kV |
95 |
10 |
Rated lightning impulse withstand voltage |
185 |
|
11 |
Mechanical life |
Times |
10000 |
12 |
Rated single capacitor bank switching current |
A |
630 |
13 |
Rated back-to-back capacitor bank current |
400 |
|
14 |
Rated voltage of energy storage motor |
V |
AC/DC 220/110 |
15 |
Power of energy storage motor |
W |
≤230 |
16 |
Energy storage time |
s |
≤15 |
17 |
Ratea voltage of closing/opening coil |
V |
DC 220/110 |
18 |
Rated current of closing/opening coil |
A |
1.05(110V) 0.96(220V) |
19 |
Clearance between open contacts |
mm |
20±2 |
20 |
Contact travel |
7.5±1.5 |
|
21 |
Three phase opening and closing asynchronism |
ms |
≤2 |
22 |
Contact closing bounce time |
≤3 |
|
23 |
Main circuit resistance (not include contact arm) |
μΩ |
≤40 |