CJ20 AC Contactor

Short Description:

CJ20 AC contactor ( AC/DC contactor), mainly used in the circuit of AC 50Hz (or 60Hz), rated voltage to 660V, rated operating current to 630A, for long-distance making and breaking circuit, and combination with the appropriate thermal overload relay, to protect the circuit that operation may overload. AC/DC contactor meets standards of IEC60947-4-1, GB14048.4.


Product Detail

Product Tags

Scope of Application

CJ20 AC contactor ( AC/DC contactor), mainly used in the circuit of AC 50Hz (or 60Hz), rated voltage to 660V, rated operating current to 630A, for long-distance making and breaking circuit, and combination with the appropriate thermal overload relay, to protect the circuit that operation may overload. AC/DC contactor meets standards of IEC60947-4-1, GB14048.4.

Model and meaning

图片1

Normal operating conditions and installation conditions

Ambient air temperature: -5℃~+40℃, the average does not exceed +35℃ within 24 hours.
Altitude: not more than 2000m.
Atmospheric conditions: the maximum temperature is +40℃, the relative humidity is not more than 50%; at lower temperatures can allow a higher relative humidity, for example, +20℃ up to 90%, special measures should be taken for condensation produced occasionally due to temperature changes.
Pollution level: 3.
Installation category: Ⅲ.
Installation conditions: The inclination of the installation surface and the vertical plane is not more than ±5°.
Shock Vibration: The AC/DC contactor should be installed and used in the place without significant shaking, shock and vibration.

Main parameters and technical performance

Coil rated control supply voltage Us is: AC 50Hz, 110V, 127V, 220V, 380V; DC: 110V, 220V
Mechanical life: CJ20-10,16,25,40,63,100,160 for the 10 million times, CJ20-250,400,630 for the 6 million times.
Saving rate of energy-saving AC/DC contact(see Table 1).
Table 1

Model

CJ20-63~160JZ

CJ20-630J

CJ20-250~630JZ

Saving rate %

90

95

95

Main parameters and technical performance of contactor (see Table 2).
Table 2

Model

Rated insulation voltage

Ui(V)

Conventional free air

heating current Ith(A)

Maximum power of

three phase squirrel

cage motor controlled by

AC-3 kW

Number of operating

cycles per hour

times/h(AC-3)

AC-3

Electrical life

(10000 times)

Coil power

Start / Hold

VA/VA

Selection of fuses

(SCPD) models

220V

380V

660V

CJ20-10

690

10

2.2

4

4

1200

100

65/9

RT16-20

CJ20-16

16

4.5

7.5

11

62/9

RT16-32

CJ20-25

25

5.5

11

13

93/14

RT16-50

CJ20-40

32

11

22

22

175/19

RT16-80

CJ20-63

40

18

30

35

120

480/57

RT16-160

CJ20-100

63

28

50

50

570/61

RT16-250

CJ20-160

100

48

85

85

855/85.5

RT16-315

CJ20-250

250

80

132

-

600

60

1710/152

RT16-400

CJ20-400

400

115

200

200

1710/250

RT16-500

CJ20-630

630

175

300

-

3578/91.2

RT16-630

Contact type, quantity and basic parameters of auxiliary contacts (see Table 3)
Table 3

Model

Conventional free air

heating current(A)

Rated insulation voltage(V)

Rated operating

voltage(V)

Rated operating

current(A)

Rated control capacity

Types and number

of contact

AC

DC

AC

DC

AC

DC

CJ20-10~40

10

690

380

220

0.26

0.14

AC-15

100VA

DC-13

30W

Two normally open,

two normally closed

220

110

0.45

0.27

CJ20-63~160

10

380

220

0.80

0.27

AC-15

300VA

DC-13

60W

Two normally open,

two normally closed

220

110

1.4

0.6

CJ20-250~630

10

380

220

1.3

0.27

AC-15

500VA

DC-13

60W

normally open 4 3 2

220

110

2.3

0.6

normally closed 2 3 4

Wiring diagram

图片2

Structural features

Contact system of AC/DC contactor for the arrangement of direct-acting and double-break, auxiliary contact of CJ20-40A and more as separate component installed in the both sides of the main contact, is separation in the electrical.
CJ20-10~25A AC/DC contactors can be installed with screws or 35mm standard card rails.
CJ20-10~16A AC/DC contactors use a double breakpoint simple opening arc chamber, and the rest use multi-longitudinal seam arcing cover or arcing cover enclosures, with high breaking capacity, high reliability.
CJ20-63~630 energy-saving AC/DC contactors have DC general power-saving module, not only can derive muffler energy-saving products or DC operation products, and do not take up auxiliary contacts, thus greatly improving product reliability and life.

Outline and installation dimensions

图片3

Keywords: CJ20 ,DC contactor,Din Rail Mounted Contactor


  • Previous:
  • Next:

  • Write your message here and send it to us