CJ20 AC Contactor
Scope of Application
CJ20 AC contactor ( AC/DC contactor), mainly used in the circuit of AC 50Hz (or 60Hz), rated voltage to 660V, rated operating current to 630A, for long-distance making and breaking circuit, and combination with the appropriate thermal overload relay, to protect the circuit that operation may overload. AC/DC contactor meets standards of IEC60947-4-1, GB14048.4.
Model and meaning

Normal operating conditions and installation conditions
Ambient air temperature: -5℃~+40℃, the average does not exceed +35℃ within 24 hours.
Altitude: not more than 2000m.
Atmospheric conditions: the maximum temperature is +40℃, the relative humidity is not more than 50%; at lower temperatures can allow a higher relative humidity, for example, +20℃ up to 90%, special measures should be taken for condensation produced occasionally due to temperature changes.
Pollution level: 3.
Installation category: Ⅲ.
Installation conditions: The inclination of the installation surface and the vertical plane is not more than ±5°.
Shock Vibration: The AC/DC contactor should be installed and used in the place without significant shaking, shock and vibration.
Main parameters and technical performance
Coil rated control supply voltage Us is: AC 50Hz, 110V, 127V, 220V, 380V; DC: 110V, 220V
Mechanical life: CJ20-10,16,25,40,63,100,160 for the 10 million times, CJ20-250,400,630 for the 6 million times.
Saving rate of energy-saving AC/DC contact(see Table 1).
Table 1
Model |
CJ20-63~160JZ |
CJ20-630J |
CJ20-250~630JZ |
Saving rate % |
90 |
95 |
95 |
Main parameters and technical performance of contactor (see Table 2).
Table 2
Model |
Rated insulation voltage Ui(V) |
Conventional free air heating current Ith(A) |
Maximum power of three phase squirrel cage motor controlled by AC-3 kW |
Number of operating cycles per hour times/h(AC-3) |
AC-3 Electrical life (10000 times) |
Coil power Start / Hold VA/VA |
Selection of fuses (SCPD) models |
||
220V |
380V |
660V |
|||||||
CJ20-10 |
690 |
10 |
2.2 |
4 |
4 |
1200 |
100 |
65/9 |
RT16-20 |
CJ20-16 |
16 |
4.5 |
7.5 |
11 |
62/9 |
RT16-32 |
|||
CJ20-25 |
25 |
5.5 |
11 |
13 |
93/14 |
RT16-50 |
|||
CJ20-40 |
32 |
11 |
22 |
22 |
175/19 |
RT16-80 |
|||
CJ20-63 |
40 |
18 |
30 |
35 |
120 |
480/57 |
RT16-160 |
||
CJ20-100 |
63 |
28 |
50 |
50 |
570/61 |
RT16-250 |
|||
CJ20-160 |
100 |
48 |
85 |
85 |
855/85.5 |
RT16-315 |
|||
CJ20-250 |
250 |
80 |
132 |
- |
600 |
60 |
1710/152 |
RT16-400 |
|
CJ20-400 |
400 |
115 |
200 |
200 |
1710/250 |
RT16-500 |
|||
CJ20-630 |
630 |
175 |
300 |
- |
3578/91.2 |
RT16-630 |
Contact type, quantity and basic parameters of auxiliary contacts (see Table 3)
Table 3
Model |
Conventional free air heating current(A) |
Rated insulation voltage(V) |
Rated operating voltage(V) |
Rated operating current(A) |
Rated control capacity |
Types and number of contact |
|||
AC |
DC |
AC |
DC |
AC |
DC |
||||
CJ20-10~40 |
10 |
690 |
380 |
220 |
0.26 |
0.14 |
AC-15 100VA |
DC-13 30W |
Two normally open, two normally closed |
220 |
110 |
0.45 |
0.27 |
||||||
CJ20-63~160 |
10 |
380 |
220 |
0.80 |
0.27 |
AC-15 300VA |
DC-13 60W |
Two normally open, two normally closed |
|
220 |
110 |
1.4 |
0.6 |
||||||
CJ20-250~630 |
10 |
380 |
220 |
1.3 |
0.27 |
AC-15 500VA |
DC-13 60W |
normally open 4 3 2 |
|
220 |
110 |
2.3 |
0.6 |
normally closed 2 3 4 |
Wiring diagram

Structural features
Contact system of AC/DC contactor for the arrangement of direct-acting and double-break, auxiliary contact of CJ20-40A and more as separate component installed in the both sides of the main contact, is separation in the electrical.
CJ20-10~25A AC/DC contactors can be installed with screws or 35mm standard card rails.
CJ20-10~16A AC/DC contactors use a double breakpoint simple opening arc chamber, and the rest use multi-longitudinal seam arcing cover or arcing cover enclosures, with high breaking capacity, high reliability.
CJ20-63~630 energy-saving AC/DC contactors have DC general power-saving module, not only can derive muffler energy-saving products or DC operation products, and do not take up auxiliary contacts, thus greatly improving product reliability and life.
Outline and installation dimensions

Keywords: CJ20 ,DC contactor,Din Rail Mounted Contactor